What causes uneven currents in VFD motors?

What is the probem from a friend :

A 185kW electric motor, powered by a 220kW inverter, the electric motor runs with U-phase current about half of V-phase and W-phase, works fine, and alarms several times a day!

When the U phase was changed to V phase, the V phase current was again about half of the U and W phases.

Regarding the problem of uneven current in three-phase motors,

which is encountered both in use and in tests, we can screen by changing the conditions. For the sake of understanding, we will start with the analysis of the industrial frequency motor.

If the current is uneven, we can detect it by way of input voltage, so that we can distinguish whether it is a power supply problem or a motor problem.

If the power supply voltage is uneven, we can exclude the electric motor problem; on the contrary, if the voltage is not a problem, we can determine that it is a electric motor problem.

If it is not convenient to measure the voltage, it can be judged by inverting the phase.

If the current is abnormal after inverting the phase and shifting with the inverted phase, it is generally a power supply problem, otherwise, it is an electric motor problem.

As for the VFD motor, the inverter is added between the power supply and the motor, and the abnormality of the inverter can also lead to abnormal operation.

We can make a basic judgment by the balance of the inverter input and output voltage, but also by replacing the inverter or disconnecting the inverter measures to the screen.

As far as the motor itself is concerned, when there is a serious imbalance in the three-phase current, the motor winding temperature will rise significantly, accompanied by the abnormal sound.

Thus, for motors powered through inverters, when there are data abnormalities, it is possible that there is a problem with the variable power supply or a problem with the data feedback system.

The common faults of inverters are divided into main circuit faults and auxiliary control circuit faults.

Among them, main circuit faults include rectifier block damage, charging resistor damage and inverter module burnout; auxiliary control circuit faults include drive circuit faults, switching power supply damage and feedback, detection circuit faults, etc.

All these faults will lead to abnormal motor power supply and feedback.

It is a very important to find a professional electric motor manufacturer to save the time.

Dongchun motor is a professional fabrikantof electric motors inChina.

Please kindly check the products as follows

enkele fase motor: Yc, ycl met gietijzeren lichaam en ml, mijn motor met aluminium lichaam

Driefasige motor : IE1, IE2, IE3 Motor voor zowel gietijzeren lichaam als aluminium lichaam

Remmotor: DC -remmotor en AC -remmotor

VFD MotoR: Frequentievariabele aandrijfmotoren.

Get a Free quote from Dongchun motor

Laat een antwoord achter

Uw e -mailadres wordt niet gepubliceerd. Vereiste velden zijn gemarkeerd *

Boost uw bedrijf met onze hoogwaardige diensten

Vraag om een ​​snel citaat

Bedankt voor uw bericht, we nemen binnen 1 werkdag contact met u op.

Vraag om een ​​snelle catalogus

Bedankt voor uw bericht, we nemen binnen 1 werkdag contact met u op.

Vraag om een ​​snel citaat

Bedankt voor uw bericht, we nemen binnen 1 werkdag contact met u op.

Vraag om een ​​snel citaat

Bedankt voor uw bericht, we nemen binnen 1 werkdag contact met u op.

× Hoe kan ik u helpen?